The indoor temperature is using a different interface (the indoor interface) compared to all other reading/writing to the heatpump and is thus “independent”. If the interface is not connected/lost the heatpump will report 20 degrees as the “actuall”. When ThermIQ-room2 is reset it will use 20.5 as it’s default and as a way to distinguish that a connection is made.
The interface is very thermia specific and there is no obvious connection to the decimal values 0.6 / 0.7
I have verified on my pump that the following range of indoor temperature works with indoor wanted set to 22:
ThermIQ/ThermIQ-room2-jas/set
{“INDR_T”: 20.0 } – {“INDR_T”: 23.8 }
and fails for 22.7, 23.6 and 23.7 with indoor target set to 23. It does work for 22.6
I do not see that the interface hangs, I can transmitt a new value and it is received properly. An hung ThermIQ should always return to working state by sending reset to it.
I will look deeper into this, it is not a bug in the calculation of values since 22.6 is transferred correctly but some interference between values or in transmission of values. It could also be a bug in the heatpump but that would be unexpected…
-