Thermia Diplomat Optimum G3 – EVU workings

Shop › Forum › ThermIQ-MQTT, Nodered and Home Assistant › Thermia Diplomat Optimum G3 – EVU workings

Visar 2 inlägg - 1 till 2 (av 2 totalt)
  • Författare
    Inlägg
  • #8844
    jobelz
    Deltagare

    Good day!

    I finally got around to installing the Thermiq MQTT/ROOM2 and all is working well. The only thing that’s unclear right now is if setting EVU = 1 should stop a running compressor? Or does this only block the starting of the compressor. Right now, it doesn’t seem to stop the heatpump when it’s working. Is that expected for this model? Or is there a way to ”unlock” this behavior?

    Thank you for creating this hardware, it’s going to save me a lot of headaches this winter!

    Kind regards,
    Johan

    #8846
    Anders a
    Keymaster

    EVU=1 stops the heatpump regardless of current mode and settings. Please check your wire connections. They are polarized and cannot be switched.

    • Det här svaret redigerades för 20 timmar, 50 minuter sedan av Anders a.